All Orrcon Steel products for the fire protection market have ActivFire® Scheme approval and are listed under the register of fire protection equipment.
 
ACTIVFIRE® Scheme is your assurance that our products have met the stringent requirements of CSIRO’s accreditation process.

All products are deemed to comply with the following standards:

  • AS 2419.1 - Fire Hydrant Instalations
  • AS 4118.2.1 - Fire Sprinkler Systems - Piping - General
  • AS 1074 - Steel tubes and tubulars for ordinary services

 
It includes the following objectives:

  • To verify the conformity (compliance) of equipment through physical testing and appraisal to relevant and endorsed standards and specifications (reference criteria).
  • To verify and recognise approvals and certifications by other national and International bodies.
  • To provide an effective and transparent mechanism for appraisal, testing, certification and listing of emerging and new technologies in the field of active fire protection equipment and systems.
  • To provide reference documentation and information which supports the various building regulation and authority requirements for “evidence of suitability” for equipment used in building construction.
  • To maintain a continuing process that provides means by which the conformity of changes to products can be submitted and verified.
  • To maintain a Register of Fire Protection Equipment to publicly list and promote products which meet established reference criteria for listing.

 
Procedures and mechanisms for monitoring compliance and performance can vary. Listed products are identified in the Register of Fire Protection Equipment.
 
This resource exists primarily as an on-line database accessed through the website www.activfire.gov.au.

FIREPIPE COATINGS INFO

ACTIVFIRE® Info

Product Designation ACTIVFIRE® Scheme Approval Listing Number
ORRFIRE® SMARTCOTE® Painted Red Extra Light pipe AFP 1641
ORRFIRE® SMARTCOTE® Painted Red  Light pipe AFP 1510
ORRFIRE® SMARTCOTE® Painted Red  Medium pipe AFP 1511
ORRFIRE® ALLGAL® Zinc Coated Extra Light pipe AFP 1640
ORRFIRE® ALLGAL® Zinc Coated Light pipe AFP 1508
ORRFIRE® ALLGAL® Zinc Coated Medium pipe AFP 1509

Diameter Range (mm)
Nominal Bore Diameter (NB) 20 25 32 40 50 65 80 100 125 150   200 250 300
Outside Diameter (OD) 26.9 33.7 42.4 48.3 60.3 76.1 88.9 114.3 139.7 165.1 168.3 219.1 273.1 323.9
Minimum OD 26.63 33.36 41.98 47.82 59.70 75.34 88.01 113.16 138.30 163.45 166.62 216.91 270.37 320.66
Maximum OD 27.17 34.04 42.82 48.78 60.90 76.86 89.79 115.44 141.10 166.75 169.98 211.29 275.83 327.14

Note: Outside Diameter is fixed for all wall thicknesses.

 

Pipe Dimensions Minimum Yield Strength Minimum Tensile Strength Minimum Elongation as a proportion of gauge length
Light Wall Pipe 20 TO 150 NB (3/4 TO 6 INCH) 350 MPa 430 MPa 20%
Medium Wall Pipe 20 TO 150 NB (3/4 TO 6 INCH) 250 MPa 350 MPa 20%
Schedule 200 TO 300 NB (8 TO 12 INCH) 350 MPa 430 MPa 20%

End Treatment Min Diameter (mm) Max Diameter (mm) Min Thickness (mm) Max Thickness (mm)
Threading 25NB 50NB 3.2 4.5

End Treatment Diameter (mm) Min Thickness* (mm) Max Thickness (mm)
Roll Grooving 50NB 2.3 3.6
65NB 2.3 3.6
80NB 2.6 4.0
100NB 2.5 4.5
125NB 3.0
150NB 3.0
200NB 4.8
250NB 4.8

Note:

  • *Contact your Orrcon Steel Representative for minimum thicknesses outside the listed range.
  • ◆ Contact your Orrcon Steel Representative for maximum thicknesses which are not listed for the specified diameter pipe.